Product Description
|
Specifications
|
||
|---|---|---|
| Model / Code | SLC‑200‑CUBE3+ B1 | |
| Rated Power (VA / W) | 200,000 VA / 180,000 W | |
| Technology | On‑line double conversion (VFI), high‑frequency (HF), DSP controlled | |
| Input Type | 3‑Phase + Neutral | |
| Input Nominal Voltage | 3 × 380 V / 3 × 400 V / 3 × 415 V (3F + N) | |
| Input Voltage Range | +15% / –20% (configurable) | |
| Input Frequency (Nominal) | 50 Hz / 60 Hz | |
| Input THDi (Distortion) | < 1.5% at 100% load; < 2.5% at 50% load; < 6.0% at 10% load | |
| Input Power Factor | ≈ 1 from ~10% load | |
| Output Voltage (Nominal) | 3 × 380 V / 3 × 400 V / 3 × 415 V (3F + N) | |
| Output Power Factor | 0.9 | |
| Static Output Accuracy | ± 1% | |
| Dynamic Output Accuracy | ± 2% | |
| Output THDv (Distortion) | < 0.5% for linear load; < 1.5% for non‑linear load | |
| Efficiency (On‑line Mode) | ~94.0%–95.0% | |
| Eco‑Mode Efficiency | ~98%+ | |
| Crest Factor | 3 : 1 | |
| Overload Capability | 125% for 10 min; 150% for 60 s; >150% for 20 ms | |
| Battery Type Compatibility | Lead‑acid, sealed, maintenance‑free | |
| Communication Interfaces | RS‑232/RS‑485 + USB; Modbus supported; intelligent slot for SNMP | |
| Parallel Operation Capability | Up to 4 units | |
| Operating Temperature | 0 °C to +40 °C | |
| Relative Humidity | Up to 95% non‑condensing | |
| Maximum Operating Altitude | Up to 2,400 m (without derating) | |
| Dimensions (W × D × H) | Approximately 900 mm × 850 mm × 1,900 mm | |
| Weight | Approximately 550 kg | |
| Certifications / Standards | IEC/EN 62040‑1; IEC/EN 62040‑2; EN/IEC 62040‑3 (VFI‑SS‑11) | |
| Model Variant | “B1” designation meaning “with extra charger” / designed for external battery banks | |
General Inquiries
There are no inquiries yet.