Product Description
|
Specifications
|
||
|---|---|---|
| Model / Code | SLC‑8000‑TWIN PRO2 / 699CB000004 | |
| Rated Power (VA / W) | 8,000 VA / 8,000 W | |
| Output Power Factor | 1.0 (kW = kVA) | |
| Technology | On‑line double conversion (VFI) | |
| Format | Tower format | |
| Input Rated Voltage | 220 V / 230 V / 240 V | |
| Input Voltage Range | 110 V ÷ 276 V (at 50% load) | |
| Input Frequency (Nominal) | 50 Hz / 60 Hz | |
| Input Frequency Range | ±10% | |
| Input THDi (Total Harmonic Distortion) | <4% | |
| Input Power Factor | ≥0.99 | |
| Output Voltage (Nominal) | 208 V / 220 V / 230 V / 240 V | |
| Static Output Accuracy | ±1% | |
| Output THDv (Linear Load) | ≤1% | |
| Output THDv (Non‑Linear Load) | ≤4% | |
| Efficiency (Online Mode) | ~93% to 94% | |
| Admissible Overloads | Up to 110% for 10 minutes; up to 130% for 1 minute | |
| Crest Factor | 3 : 1 | |
| Parallel Operation Capability | Yes — up to 3 units | |
| Battery Type | Sealed Pb‑Ca (AGM), maintenance‑free | |
| Battery Recharge Time | 7 to 9 hours to 90% charge | |
| Operating Temperature | 0 °C to +40 °C | |
| Relative Humidity | Up to 95% non‑condensing | |
| Maximum Operating Altitude | Up to 2,400 m (with power degradation beyond) | |
| Dimensions (W × D × H) | 250 mm (Width) × 592 mm (Depth) × 576 mm (Height) | |
| Weight | 84 kg | |
| Standards / Certifications | Safety: EN/IEC 62040‑1; EMC: EN/IEC 62040‑2 (C3); Operation: EN/IEC 62040‑3 (VFI‑SS‑11) | |