Product Description
|
Specifications
|
||
|---|---|---|
| Model / Code | SLC‑6000‑TWIN RT2 B1 | |
| Rated Power (VA / W) | 6,000 VA / 6,000 W | |
| Technology | On‑line double conversion (VFI) | |
| Format | Convertible: Tower or Rack | |
| Input Rated Voltage | 220 / 230 / 240 V | |
| Input Voltage Range | 110 V to 300 V (up to ~50% load) | |
| Input Frequency (Nominal) | 50 / 60 Hz (auto‑detection) | |
| Input Frequency Range | ±4 Hz | |
| Input Total Harmonic Distortion (THDi) | ≤ ~4% | |
| Input Power Factor | >0.99 at full load; ~0.97 at 50% load | |
| Output Power Factor | 1.0 (kW = kVA) | |
| Output Voltage (Nominal) | 208 / 220 / 230 / 240 V | |
| Output Static Accuracy | ±1% | |
| Output Total Harmonic Distortion (THDv) – Linear Load | < 1% | |
| Output THDv – Non‑Linear Load | < 4% | |
| Efficiency (Online Mode) | ~93‑94% | |
| Eco‑Mode Efficiency | ≥ 99% | |
| Overload Capability | <110% for 10 min; <130% for 1 min; >130% for 1 s | |
| Parallel Operation Capability | Yes – up to 3 units in parallel | |
| Battery/Charger Info | Does not include internal batteries; external battery bank required | |
| Recharge Time | ~7‑9 hours to 90% charge | |
| Operating Temperature | 0 °C to +40 °C | |
| Relative Humidity | Up to 95% (non‑condensing) | |
| Maximum Operating Altitude | Up to ~2,400 m above sea level without extra derating | |
| Dimensions (W × D × H) | 438 mm (Width) × 630 mm (Depth) × 88 mm (Height) | |
| Weight | ~18 kg | |
| Standards / Certifications | IEC/EN 62040‑1; IEC/EN 62040‑2 (C3); EN/IEC 62040‑3 (VFI‑SS‑11) | |
General Inquiries
There are no inquiries yet.