Product Description
|
Specifications
|
||
|---|---|---|
| Model / Code | SLC‑3000‑TWIN RT2 B1 / 698CA000010 | |
| Rated Power (VA / W) | 3,000 VA / 3,000 W | |
| Output Power Factor | 1.0 (kW = kVA) | |
| Technology | On‑line double conversion (VFI) | |
| Format | Convertible Tower / Rack (2U height) | |
| Input Rated Voltage | 200 V / 208 V / 220 V / 230 V / 240 V | |
| Input Voltage Range | 110 V to 300 V (up to ~60% load) | |
| Input Frequency (Nominal) | 50 / 60 Hz | |
| Input Frequency Range | ±10 Hz | |
| Input THDi (Distortion) | ≤ 5% | |
| Output Rated Voltage | 200 V / 208 V / 220 V / 230 V / 240 V | |
| Output Voltage Accuracy | ±1% | |
| Output THDv (Distortion) | < 2% (linear load) / < 4% (non‑linear load) | |
| Efficiency (Online Mode) | ≥ 89% – 91% | |
| Efficiency (Eco Mode) | ≥ 95% – 97% | |
| Admissible Overloads | < 130% for 5 minutes; < 140% for 30 seconds; < 150% for 1.5 seconds | |
| Number of Output Sockets | 8 + 1 | |
| Programmable Sockets | Yes — 4 critical / 4 non‑critical loads | |
| Battery Type Compatibility | No internal batteries included; sealed Pb‑Ca / AGM recommended | |
| Recharge Time | ~3 hours to 95% (with proper batteries) | |
| Communication Interfaces | USB‑HID, RS‑232; intelligent slot (for SNMP / MODBUS / potential‑free contacts) | |
| Cold Start | Yes | |
| Emergency Stop (EPO) | Yes | |
| Operating Temperature | 0 °C to +55 °C | |
| Relative Humidity | Up to 95% (non‑condensing) | |
| Maximum Operating Altitude | Up to approx. 2,400 m (with derating beyond) | |
| Noise Level | < 55 dB at 1 metre | |
| Dimensions (W × D × H) | 438 mm (W) × 605 mm (D) × 88 mm (H) | |
| Weight | ~12.4 kg | |
| Standards / Certifications | EN/IEC 62040‑1 (safety); EN/IEC 62040‑2 (EMC, C2); EN/IEC 62040‑3 (VFI‑SS‑11) | |
General Inquiries