| Model / Code | SLC‑160‑CUBE3+ B1 / 681TE000001 | |
| Rated Power (VA / W) | 160,000 VA / 140,000 W | |
| Technology | On‑line, double conversion (VFI), high‑frequency (HF), DSP control | |
| Input Type | 3‑Phase + Neutral | |
| Input Nominal Voltage | 3 × 380 V / 3 × 400 V / 3 × 415 V | |
| Input Voltage Range | +15% / ‑20% (configurable) | |
| Input Frequency (Nominal) | 50 / 60 Hz | |
| Input THDi (Distortion) | At 100% load: < 1.5% ; at 50% load: < 2.5% ; at 10% load: < 6% | |
| Input Power Factor | ≈ 1 from 10% load | |
| Output Voltage (Nominal) | 3 × 380 V / 3 × 400 V / 3 × 415 V (3F + N) | |
| Output Power Factor | 0.9 | |
| Static Output Accuracy | ±1% | |
| Dynamic Output Accuracy | ±2% | |
| Output Distortion (THDv) | < 0.5% (linear load) ; < 1.5% (non‑linear load) | |
| Efficiency (On‑line Mode) | ~94‑95% (for 80‑200 kVA class) | |
| Efficiency (Eco/Standby Mode) | Up to ~98% | |
| Crest Factor | 3:1 | |
| Overload Capability | 125% for 10 minutes; 150% for 60 seconds; >150% for 20 ms | |
| Communication / Interfaces | RS‑232/RS‑485 + USB; intelligent slot for SNMP/NIMBUS etc. | |
| Parallel Operation Capability | Up to 4 units in parallel | |
| Operating Temperature | 0 °C to +40 °C | |
| Relative Humidity | Up to 95% non‑condensing | |
| Maximum Operating Altitude | Up to ~2,400 m (without derating) | |
| Dimensions (W × D × H) | 900 mm × 855‑900 mm × 1,905 mm (approx.) | |
| Weight | ~540 kg | |
| Certifications / Standards | IEC/EN 62040‑1 ; IEC/EN 62040‑2 (C3) ; EN/IEC 62040‑3 VFI‑SS‑11 | |
| Battery/Extra Charger | “With extra charger” version (B1) – designed for large external battery banks | |