Product Description

Standard Model Battery Type 12 V / 7 AH
Numbers 16
Typical Recharge Time 9 Hours Recover to 90% Capacity
Charging Current (max.) 1.0 A
Charging Voltage 218.4 VDC ± 1%
Standard Model Battery Type 12 V / 7 AH
Numbers 16
Typical Recharge Time 9 Hours Recover to 90% Capacity
Charging Current (max.) 1.0 A
Charging Voltage 218.4 VDC ± 1%
Long Run Model Battery Type Depending on Applications
Numbers 16-20**
Charging Current (max.) 4.0 A
Charging Voltage (13.65VDC x Battery Number) ± 1%
Standard Model

 

Dimension D X W X H (mm) 369 x 190 x 688
Net Weight (kgs) 54
Long-run Model Dimension D X W X H (mm) 369 x 190 x 318
Net Weight (kgs) 13

 

 

TECHNICAL SPECIFICATIONS

Model

E006GER31

Phase

Single phase with ground

Capacity

6000 VA / 6000 W

INPUT

Nominal Voltage

208/220/230/240 VAC

Voltage Range

110~300VAC ± 3 % at 50% Load, 176~300VAC ± 3 % at 100% Load

Frequency Range

46~54 Hz or 56~64 Hz

Harmonic Distortion(THDi)

< 4% @100% Load, < 6% @50% Load

Power Factor

≧ 0.99 @ Full Load

OUTPUT

Output Voltage

208*/220/230/240 VAC

AC Voltage Regulation (Batt.
Mode)

± 1%

Frequency Range (Synchronized Range)

46~54 Hz or 56~64 Hz

Frequency Range
(Batt. Mode)

50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz

Current Crest Ratio

3:1 (max.)

Harmonic Distortion

≦1 % THD (Linear Load), ≦ 4 % THD (Non-linear Load)

Transfer Time – AC Mode to Battery Mode

Zero

Transfer Time – Inverter to Bypass

Zero

Waveform (Batt. Mode)

Pure Sinewave

Overload – AC Mode

100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec

Overload – Inverter to Bypass

100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec

EFFICIENCY

AC Mode

94%

Battery Mode

91%

ENVIRONMENT

Operation Humidity

20-90 % RH @ 0- 40°C (non-condensing)

Noise Level

Less than 55dBA @ 1 Meter

MANAGEMENT

Smart RS-232 / USB

Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and MAC

Optional SNMP