ExTell E002GER31 Galaxy, Rack Mount Single Phase External Battery 2 KVA Online UPS – Black Price in Dubai UAE
- Unity Power Factor
- True Double Conversion
- EPO Function
- Network Manageable
- ECO Mode for Energy Saving
- Low THDi to reduce power system pollution
- Adjustible charging current
Product Description
TECHNICAL SPECIFICATIONS
Model
E002GER31
Phase
Single phase with ground
Capacity
2000 VA / 2000 W
INPUT
Nominal Voltage
100/110/115/120 /127 VAC or 200/208/220/230/240 VAC
Voltage Range
55-150 VAC ± 5% or 110-300 VAC ± 5% @ 50% Load, 80-150 VAC ± 5% or 160-300 VAC ± 5% @ 100% Load
Frequency Range
40Hz ~ 70Hz
Harmonic Distortion(THDi)
≦5% @ Nominal Input Voltage
Power Factor
≧ 0.99 @ Nominal Voltage (100% load)
OUTPUT
Output Voltage
100*/110*/115*/120/127 VAC or 200*/208*/220/230/240 VAC
AC Voltage Regulation (Batt.
Mode)
± 1%
Frequency Range (Synchronized Range)
57 ~ 63 Hz or 47 ~ 53 Hz
Frequency Range
(Batt. Mode)
60Hz ± 0.1Hz or 50 Hz ± 0.1Hz
Current Crest Ratio
3:1 (max.)
Harmonic Distortion
≦ 2 % THD (Linear Load); ≦ 4 % THD (Non-Linear Load)
Transfer Time – AC Mode to Battery Mode
Zero
Transfer Time – Inverter to Bypass
4 ms (Typical)
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
AC Mode
≧91% @ Full Charged Battery
ECO Mode
≧ 96% @ Full Charged Battery
Battery Mode
≧90%
BATTERY
Battery Type
12 V / 9 AH – 12 V / 7 AH
Numbers
4 – 6
Typical Recharge Time
3 Hours Recover to 95% Capacity for Internal Battery@ 2A Charging Current
Charging Current
100/110/115/120 /127 VAC Models: Default 2A, Max. 8A Adjustable
200/208/220/230/240 VAC Models: Default 2A, Max. 12A Adjustable
Charging Voltage
54.8 VDC ±1% – 82.1 VDC ±1%
PHYSICAL
Dimension, D X W X H (mm)
510 x 438 x 88 – 630 x 438 x 88
Net Weight (without battery) (kgs)
9.4 – 10.6
Net Weight (with battery) (kgs)
19.5 – 23.3
ENVIRONMENT
Humidity
20-90 % RH @ 0- 40°C (Non-Condensing)
Noise Level
Less than 50dBA @ 1 Meter
Altitude
10% de-rating for over 1000m (The altitude should not exceed 3000m)
MANAGEMENT
Smart RS-232 / USB
Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux and MAC
Optional SNMP
Power management from SNMP manager and web browser
General Inquiries
There are no inquiries yet.
Reviews