Product Description
|
Specifications
|
||
|---|---|---|
| Model Name | APC E3SUPS30KHB2 Easy UPS 3S 30 kVA 400 V 3:3 | |
| Product Type | Online Double‑Conversion UPS | |
| Rated Power | 30 kVA / 30 kW | |
| UPS Topology | Double‑conversion (online) | |
| Input Phase | 3‑phase | |
| Nominal Input Voltage | 400 V AC 3‑phase | |
| Input Voltage Range | 304 – 477 V AC | |
| Input Frequency Range | 45 – 65 Hz | |
| Input Power Factor | ~0.99 | |
| Output Phase | 3‑phase | |
| Nominal Output Voltage | 380/400/415 V AC | |
| Output Frequency | 50/60 Hz (synchronized to mains) | |
| Output Waveform | Pure sine wave | |
| Output Voltage Distortion (THD) | < 3 % (linear load) | |
| Output Power Factor | ~1.0 | |
| Overload Capability | 125 % for 10 min / 150 % for 1 min | |
| Battery Type | Internal VRLA modular batteries | |
| Included Battery Modules | 4 × 7 Ah VRLA modular battery strings | |
| Nominal Battery Voltage | ~240 V DC | |
| Estimated Backup Time | Higher runtime due to four battery strings (varies with load) | |
| Maximum Short‑Circuit Current | ~10 kA | |
| Communication & Management | RS232, RS485, USB, dry contacts; optional network management | |
| Display / Interface | Multifunction LCD/LED display | |
| Bypass | Built‑in maintenance bypass | |
| Efficiency | ~95 % (online conversion); higher in ECO mode | |
| Noise Level | ~63 dBA at 1 m | |
| Protection Class | IP20 | |
| Operating Temperature | 0 – 40 °C | |
| Operating Humidity | 0 – 95 % non‑condensing | |
| Physical Colour | White | |
| Dimensions (H × W × D) | Approx. 1400 × 500 × 996 mm | |
| Net Weight | Approx. 230 kg (varies with batteries installed) | |
| Certifications / Standards | IEC 62040 series, CE, EAC, RCM, WEEE | |
| Parallel Capability | Supports parallel operation for capacity or redundancy | |
General Inquiries