Cat. 6 (250MHz), 4-Pair, F/UTP Foil shielded, Premise Horizontal Cable, 23 AWG solid bare copper conductors, Polyethylene insulation, Beldfoil® shield, AWG 26 solid tinned copper drainwire, LSZH jacket

SKU: Belden 7860ENH Category:

Product Description

Product Overview
Suitable Applications Horizontal and building backbone cable; Support current and future Category 6 and 5e applications, such as: 1000Base – T (Gigabit Ethernet), 100 Base – T, 10 Base – T, FDDI, ATM
Physical Characteristics (Overall)
CONDUCTOR
Element AWG Stranding Material No. of Pairs
Individual pair 23 Solid BC – Bare Copper 4
Conductor Count 8
Total Number of Pairs 4
INSULATION
Element Type Material Nominal Diameter
Individual pair Dielectric PE – Polyethylene 1.35 mm
Bonded-Pair Yes
COLOR CHART
Number Color
Pair 1 White/Blue & Blue
Pair 2 White/Green & Green
Pair 3 White/Orange & Orange
Pair 4 White/Brown & Brown
CABLING
Description Filler
4 pairs twisted together covered with a polyester foil Cross Web of Polyolefin
OUTER SHIELD MATERIAL
Type Material Coverage [%] Drainwire Material Drainwire AWG Drainwire Construction n x D Drainwire Position
Tape Bi-Laminate (Alum+Poly) 100% TC – Tinned Copper 26 Solid Over foil
Table Notes Aluminum facing outside in contact with drain wire
OUTER JACKET MATERIAL
Material Nominal Diameter Diameter +/- Tolerance
LSZH – Low Smoke Zero Halogen (Flame Retardant) 7.3 mm 0.3 mm
Construction and Dimensions
Min Elongation at Breakof Conductors 10 %
Min Elongation at Breakof Insulation 100 %
Min Elongation at Breakof Jacket 100 %
Min Tensile Strength of Jacket 9 MPa
Electrical Characteristics
CONDUCTOR DCR
Max. Conductor DCR Max DCR Unbalanced Between Pairs [%] Max. DCR Unbalanced Within Pair [%]
95 Ohm/km 4 % 2 %
CAPACITANCE
Max. Capacitance Unbalance Max. Mutual Capacitance
1,600 pF/km 56 pF/m
IMPEDANCE
Nominal Characteristic Impedance
100 Ohm
DELAY
Max. Delay Skew Nominal Velocity of Propagation (VP) [%]
40 ns/100m 67%
Table Notes Limits below 4 MHz are for information only. Reference standard: IEC 61156-5
General Electrical Parameters Notes Reference standard: ISO/IEC 61156-5
Coupling Attenuation Class Type II
Segregation class according EN50174-2 c
TRANSFER IMPEDANCE
Frequency [MHz] Transfer Impedance
1 Mhz Max. 50 mOhm/m
10 Mhz Max. 100 mOhm/m
30 Mhz Max. 200 mOhm/m
100 Mhz Max. 1000 mOhm/m
Transfer Impedance Class Grade 2
CURRENT
Max. Recommended Current [A]
1.5 Amps per Conductor
VOLTAGE
Voltage Rating [V]
72 V
Temperature Range
Installation Temp Range 0°C To +50°C
Operating Temp Range -30°C To +60°C
Mechanical Characteristics
Bulk Cable Weight 50 kg/km
Max. Pull Tension 80 N
Min. Bend Radius During Installation 58 mm
Min Bend Radius During Operation 29 mm
Standards
ISO/IEC Compliance ISO/IEC 11801-1
CPR Euroclass Dca-s2,d1,a1
CENELEC Compliance EN 50173-1
Data Category Category 6
ANSI Compliance ANSI/TIA 568.2-D (2018)
IEEE Compliance PoE: IEEE 802.3bt Type 1, Type 2, Type 3, Type 4
Applicable Environmental and Other Programs
Environmental Space Indoor – Euroclass Dca
EU RoHS Compliance Date (yyyy-mm-dd) 2005-01-01
Flammability, LS0H, Toxicity Testing
IEC Flammability IEC 60332-1-2
Burning Load 745 kJ/m
IEC 60754-1 – Halogen Amount Zero
IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity 2.5 µS/mm
IEC 60754-2 – Halogen Acid Gas Amount – Min. pH 4.3
IEC 61034-2 – Smoke Density Min. Transmittance 60%
Product Notes
Notes Electrical values are expected performance based on cable testing and representative performance within a typical Belden system.
History
Update and Revision Revision Number: 0.349 Revision Date: 08-27-2021
Part Numbers
Item # Color Put-Up Type Length EAN
7860ENH.03500 Black Reel 500 m 8719605016515
7860ENH.K1305 Blue Reel 305 m 8719605167859
7860ENH.01500 Blue Reel 500 m 8719605016485