| Model / Series | APC Easy UPS 3S Pro E3SP40KHB | |
| Rated Power | 40 kVA / 40 kW | |
| UPS Topology | Double‑conversion Online | |
| Phase Configuration | 3‑Phase Input / 3‑Phase Output | |
| Input Voltage | 380 / 400 / 415 V AC | |
| Input Voltage Range | ~304 – 477 V AC | |
| Input Frequency Range | 40 – 70 Hz | |
| Input Power Factor | ≥ 0.99 (at high load) | |
| Input THD | < 3 % (linear load) | |
| Output Voltage | 380 / 400 / 415 V AC | |
| Output Frequency | 50 / 60 Hz (synchronized to mains) | |
| Output Voltage Regulation | ± 1 % | |
| Output THD | < 3 % (linear load) | |
| Load Power Factor Range | 0.7 lag to 0.7 lead | |
| Overload Capability | 125 % for 10 min; 150 % for 1 min | |
| Battery Type | Internal VRLA sealed lead‑acid modules | |
| Battery Configuration | Multiple internal battery modules, expandable | |
| Nominal Battery Voltage | Dependent on internal module configuration | |
| Battery Runtime | Depends on internal battery capacity installed | |
| Battery Recharge | Automatic / Programmable charging control | |
| Bypass | Built‑in automatic & maintenance bypass | |
| Short‑Circuit Withstand Capability | Approx. 10 kA (depends on upstream protection) | |
| Display / UI | Multifunction LCD with control buttons | |
| Communications | RS‑232, RS‑485, USB, optional network management card | |
| Operating Temperature | 0 °C – 40 °C | |
| Humidity (Operating) | 0–95 % non‑condensing | |
| Altitude | Up to ~1000 m without derating | |
| Protection Class | IP20 (indoor rating) | |
| Dimensions (H × W × D) | Approx. 1400 × 500 × 940 mm | |
| Weight (Net) | Approx. 150–160 kg (varies with batteries) | |
| Standards / Certifications | IEC 62040‑1 / IEC 62040‑2 / IEC 62040‑3, CE, RoHS, WEEE | |
| Installation Type | Floor standing (tower cabinet) | |