Product Description
|
Specifications
|
||
|---|---|---|
| Model / Series | APC Easy UPS 3S E3SUPS10KH | |
| Rated Power | 10 kVA / 10 kW | |
| UPS Topology | Double‑conversion Online | |
| Phase Configuration | 3‑Phase Input / 3‑Phase Output | |
| Input Voltage | 380 / 400 / 415 V AC | |
| Input Voltage Range | ~304 – 477 V AC | |
| Input Frequency Range | 45 – 65 Hz | |
| Input Power Factor | ~0.99 at full load | |
| Input THD | < 3 % at full load | |
| Maximum Input Current | Approx. 18 A | |
| Output Voltage | 380 / 400 / 415 V AC | |
| Output Frequency | 50 / 60 Hz (synchronized to mains) | |
| Output Voltage Regulation | ± 1 % | |
| Output THD | < 3 % (linear load) | |
| Load Crest Factor | 3:1 | |
| Overload Capability | 125 % for 10 min; 150 % for 1 min | |
| Bypass | Built‑in maintenance bypass | |
| Battery Type | External battery system (batteries NOT included) | |
| Maximum Short‑Circuit Current | ~10 kA | |
| Communications / Management | RS‑485/parallel/temp sensor interface ports | |
| Efficiency (Online Mode) | High efficiency typical for class | |
| Operating Temperature | 0 °C – 40 °C | |
| Relative Humidity (Operating) | 0 – 95 % non‑condensing | |
| Altitude Rating | Up to ~1000 m without derating | |
| Protection Class | IP20 (indoor use) | |
| Audible Noise | ~60 dBA at 1 m | |
| Dimensions (H × W × D) | Approx. 530 × 250 × 700 mm | |
| Net Weight | Approx. 36 kg | |
| Certifications / Standards | IEC 62040‑1/‑2/‑3/‑4, CE, EAC, RCM, WEEE | |
General Inquiries