Product Description
Specifications
|
||
---|---|---|
Model | Salicru 698CA000003 Online Double Conversion Twin RT2 1500VA UPS | |
Technology | Online Double Conversion (True Double Conversion) | |
Format | Tower or Rack-mountable (1U) | |
INPUT | ||
Rated Voltage | 208 V / 220 V / 230 V / 240 V | |
Voltage Range (100% load) | 176 V ÷ 294 V | |
Rated Frequency | 50 / 60 Hz (auto-detection) | |
Frequency Range | ±5 Hz | |
Auto Detection of Frequency | Yes | |
Protection | Fuse or resettable thermal protection | |
OUTPUT | ||
Power Factor | 0.9 | |
Rated Voltage | 208 V / 220 V / 230 V / 240 V | |
Voltage Accuracy (Battery Mode) | ±1.5% | |
Power (VA/W) | 1500 VA / 1350 W | |
Total Harmonic Distortion (THDv) | < 2% linear load, < 5% non-linear load | |
Waveform (Battery Mode) | Pure Sine Wave | |
Frequency | 50 / 60 Hz (same as input) | |
Frequency Accuracy (Battery Mode) | ±0.1 Hz | |
Admissible Overloads in Battery Mode | < 120% for 1 minute / < 150% for 10 seconds | |
Admissible Overloads in Line Mode | < 120% for 5 minutes / < 150% for 10 seconds / >150% for 1 second | |
Socket Type | IEC (C13/C19) | |
Number of Sockets | 8 (Including programmable sockets) | |
Programmable Sockets | Yes, critical/non-critical load configuration | |
BATTERY | ||
Battery Type | Pb-Ca sealed, AGM, maintenance-free | |
Charge Type | I/U (constant current/constant voltage) | |
Recharge Time | 4 hours to 90% | |
Battery Test | Automatic at every start + weekly tests | |
CHARGER | ||
Temperature Voltage Compensation | Yes | |
COMMUNICATION | ||
Ports | RS-232 / USB-HID | |
Intelligent Slot | Yes, for SNMP / potential-free contacts / MODBUS | |
Monitoring Software | Compatible with Windows, Linux, Mac | |
INDICATIONS | ||
Type | LCD + Keypad | |
Display Values | Voltage, power, input/output frequency, battery voltage, % battery charge, % load, mode, faults, discharge time, mute | |
Operating Modes | Normal / Stabilization (AVR) / Battery / Fault | |
Alarm | Battery mode, low battery, charger failure, overload, polarity errors | |
Audible Alarm | Every 10s for battery operation. Every 2s for low battery, polarity. Every 1s for overcharge. Continuous for fault. | |
Failure Display | LCD | |
OTHER FUNCTIONS | ||
Cold Start | Yes | |
Emergency Stop (EPO) | Yes | |
ADSL/Fax/Modem Transient Protector | Yes | |
Green Function | Automatic shut-off in battery mode with load <5% | |
Smart Fan Speed | Yes, adjusts based on load | |
Site Wiring Fault | Yes, phase-neutral rotation and earth absence detection | |
GENERAL | ||
Operating Temperature | 0ºC to +40ºC | |
Relative Humidity | Up to 95%, non-condensing | |
Maximum Operating Altitude | 2400 meters above sea level (degradation up to 5000 m) | |
Acoustic Noise at 1 Meter | < 45 dB | |
STANDARDS | ||
Safety | EN IEC 62040-1 | |
Electromagnetic Compatibility (EMC) | EN IEC 62040-2 | |
Operation | EN IEC 62040-3 | |
Corporate Certification | ISO 9001, ISO 14001, ISO 45001 | |
DIMENSIONS | ||
Depth (mm) | 411 mm | |
Width (mm) | 438 mm | |
Height (mm) | 86 mm | |
WEIGHT | ||
Weight (kg) | 13.5 kg | |
Warranty | 3 years on electronics, 2 years on battery replacement |